RETFLEX-FOC® RV-K 5G25 CPR Eca
RETFLEX-FOC® RV-K 5G25 CPR Eca
RETFLEX-FOC® (RV-K)
Read more- Nexans ref. : 10272202
- EAN : 3427580738470
Description
Description
Standards
-
ProductIEC 60502
-
TestIEEE 383
Installation
These cables can be fixed on cable trays, within conduits or fixed to walls. They also can be buried directly with extra mechanical protection.
Core colours
- 2 cores = Brown + Light blue
- 3 cores = Brown + Black + Grey or Light blue + Brown + Green-Yellow
- 4 cores = Black + Grey + Brown + Light blue or Green-Yellow
- 5 cores = Black + Light blue + Brown + Grey + Green-Yellow
- > 5 cores = 1 Green-Yellow + others Black conductors numbered
Marking
Nexans 305 RV-K 0.6/1 kV UNE 21123 n(G or x) s RETFOC Eca AENOR YYYY
- n = number of cores
- G = with Green-Yellow
- x = without Green-Yellow
- s = section in mm²
- YYYY = year
Gama compatible con MOBIWAY MOB
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Flexible class 5
Conductor material
Bare copper
Insulation
XLPE (chemical)
Outer sheath
PVC
Sheath colour
Black
With Green/Yellow core
Yes
Lead free
Yes
Conductor shape
Circular
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Average insulation thickness
- mm
Number of cores
5
Conductor cross-section
25 mm²
Approximate weight
1517 kg/km
Maximum outer diameter
26.8 mm
Neutral conductor section (when smaller)
- mm²
Electrical characteristics
Electrical characteristics
Max. DC resistance of the conductor at 20°C
- Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Permissible current rating when buried
- A
Permissible current rating in open air
- A
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Flexible
Mechanical resistance to impacts
Low
Usage characteristics
Usage characteristics
Chemical resistance
Accidental
Length
- m
Max. conductor temperature in service
90 °C
Operating temperature, range
-5 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Weather resistance
Very good
Flame retardant
EN 50265-2-1
Packaging
Drum
Water proof
Good
Resources
Resources
Documentation
FAMILY EXPORT
xls — 0 B
PEP ECOPASSPORT RV-K
pdf — 4.3 MB
PEP RV-K MONO
pdf — 5.0 MB
PEP RV-K MULTI
pdf — 5.0 MB
BROCHURE MOBIWAY MOB
pdf — 3.8 MB
Current capacity table XLPE insulation single core three phase
Conductor cross-section | A1 - Insulated conductors in conduit in a thermally insulated wall | B1 - Insulated conductors in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | F - Single-core flat cables, touching in free air | Ft - Single-core trefoil cables, touching in free air | G - Single-core horizontal spaced | Gv - Single-core flat vertical spaced | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
25.0 | 95.0 | 76.0 | 117.0 | 93.0 | 119.0 | 90.0 | 96.0 | 75.0 | 107.0 | 82.0 | 141.0 | 103.0 | 135.0 | 182.0 | 103.0 | 138.0 | 161.0 | 122.0 |
Current capacity table XLPE insulation single core single phase
Conductor cross-section | A1 - Insulated conductors in conduit in a thermally insulated wall | B1 - Insulated conductors in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | F - Single-core flat cables, touching in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
25.0 | 106.0 | 84.0 | 133.0 | 105.0 | 138.0 | 101.0 | 116.0 | 90.0 | 129.0 | 98.0 | 161.0 | 121.0 |
Current capacity table XLPE insulation multicore single phase
Conductor cross-section | A2 - Multi-core cable in conduit in a thermally insulated wall | B2 - Multi-core cable in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | E - Multi-core cable in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
25.0 | 99.0 | 78.0 | 119.0 | 94.0 | 138.0 | 101.0 | 116.0 | 90.0 | 129.0 | 98.0 | 149.0 | 108.0 |
Current capacity table XLPE insulation multicore three phase
Conductor cross-section | A2 - Multi-core cable in conduit in a thermally insulated wall | B2 - Multi-core cable in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | E - Multi-core cable in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
25.0 | 89.0 | 78.0 | 105.0 | 94.0 | 119.0 | 101.0 | 116.0 | 90.0 | 107.0 | 98.0 | 149.0 | 108.0 |
Declaration of Performance
- Declaration of Performance n� : 1000232-ESPO
- Certification Date : 9/15/21
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : NB 1722
- Declared performance : Eca
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania