Nexans RV-K MOBIWAY MOB 3G1.5 D250
Nexans ref. 10279407 - Country ref. 336 -102
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 1.5 mm²
Nexans RV-K MOBIWAY MOB 3G2.5 D200
Nexans ref. 10279408 - Country ref. 336 -102
- Packaging: Drum (m)
- Number of cores: 3
- Conductor cross-section: 2.5 mm²
RET-FLEX 1x6 GL5000
Nexans ref. 10059998 - Country ref. 336 -102
- Packaging: Cut to length (m)
- Number of cores: 1
- Conductor cross-section: 6 mm²
RET-FLEX 2x1.5 GL5000
Nexans ref. 10059974 - Country ref. 336 -102
- Packaging: Cut to length (m)
- Number of cores: 2
- Conductor cross-section: 1.5 mm²
RET-FLEX 2x1.5 R100 P3km
Nexans ref. 10059973 - Country ref. 336 -102
- Packaging: Coil (m)
- Number of cores: 2
- Conductor cross-section: 1.5 mm²
Description
Description
Standards
-
ProductIEC 60502
-
TestIEEE 383
Installation
These cables can be fixed on cable trays, within conduits or fixed to walls. They also can be buried directly with extra mechanical protection.
Core colours
- 2 cores = Brown + Light blue
- 3 cores = Brown + Black + Grey or Light blue + Brown + Green-Yellow
- 4 cores = Black + Grey + Brown + Light blue or Green-Yellow
- 5 cores = Black + Light blue + Brown + Grey + Green-Yellow
- > 5 cores = 1 Green-Yellow + others Black conductors numbered
Marking
Plant nr Nexans RV-K 0.6/1 kV n(G or x) s DD YYYY UNE 21123 AC RETFOC - metric marking.
- n = number of cores
- s = section in mm²
- DD YYYY = traceability
- G = with Green-Yellow
- x = without Green-Yellow
Gama compatible con MOBIWAY MOB
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Flexible class 5
Conductor material
Bare copper
Insulation
XLPE (chemical)
Outer sheath
PVC
Conductor shape
Circular
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Neutral conductor section (when smaller)
- mm²
Electrical characteristics
Electrical characteristics
Max. DC resistance of the conductor at 20°C
- Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Flexible
Resources
Resources
Documentation
FAMILY EXPORT
xls — 0 B
PEP ECOPASSPORT RV-K
pdf — 4.3 MB
PEP RV-K MONO
pdf — 5.0 MB
PEP RV-K MULTI
pdf — 5.0 MB
BROCHURE MOBIWAY MOB
pdf — 3.8 MB
Current capacity table XLPE insulation single core three phase
Conductor cross-section | A1 - Insulated conductors in conduit in a thermally insulated wall | B1 - Insulated conductors in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | F - Single-core flat cables, touching in free air | Ft - Single-core trefoil cables, touching in free air | G - Single-core horizontal spaced | Gv - Single-core flat vertical spaced | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
Conductor cross-section 1.5 |
A1 - Insulated conductors in conduit in a thermally insulated wall
17.0 |
B1 - Insulated conductors in conduit on a wooden wall
0.0 |
C - Single-core or multi-core cable on a wooden wall
20.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
0.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
22.0 |
F - Single-core flat cables, touching in free air
0.0 |
Ft - Single-core trefoil cables, touching in free air
21.0 |
G - Single-core horizontal spaced
0.0 |
Gv - Single-core flat vertical spaced
23.0 |
mm² 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Conductor cross-section 2.5 |
A1 - Insulated conductors in conduit in a thermally insulated wall
23.0 |
B1 - Insulated conductors in conduit on a wooden wall
19.0 |
C - Single-core or multi-core cable on a wooden wall
28.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
22.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
30.0 |
F - Single-core flat cables, touching in free air
24.0 |
Ft - Single-core trefoil cables, touching in free air
28.0 |
G - Single-core horizontal spaced
22.0 |
Gv - Single-core flat vertical spaced
30.0 |
mm² 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Conductor cross-section 4.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
31.0 |
B1 - Insulated conductors in conduit on a wooden wall
25.0 |
C - Single-core or multi-core cable on a wooden wall
37.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
29.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
40.0 |
F - Single-core flat cables, touching in free air
32.0 |
Ft - Single-core trefoil cables, touching in free air
36.0 |
G - Single-core horizontal spaced
28.0 |
Gv - Single-core flat vertical spaced
39.0 |
mm² 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Conductor cross-section 6.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
40.0 |
B1 - Insulated conductors in conduit on a wooden wall
32.0 |
C - Single-core or multi-core cable on a wooden wall
48.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
38.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
52.0 |
F - Single-core flat cables, touching in free air
41.0 |
Ft - Single-core trefoil cables, touching in free air
44.0 |
G - Single-core horizontal spaced
35.0 |
Gv - Single-core flat vertical spaced
49.0 |
mm² 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Conductor cross-section 10.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
54.0 |
B1 - Insulated conductors in conduit on a wooden wall
44.0 |
C - Single-core or multi-core cable on a wooden wall
66.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
52.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
71.0 |
F - Single-core flat cables, touching in free air
57.0 |
Ft - Single-core trefoil cables, touching in free air
58.0 |
G - Single-core horizontal spaced
46.0 |
Gv - Single-core flat vertical spaced
65.0 |
mm² 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Conductor cross-section 16.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
73.0 |
B1 - Insulated conductors in conduit on a wooden wall
58.0 |
C - Single-core or multi-core cable on a wooden wall
88.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
71.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
96.0 |
F - Single-core flat cables, touching in free air
76.0 |
Ft - Single-core trefoil cables, touching in free air
75.0 |
G - Single-core horizontal spaced
59.0 |
Gv - Single-core flat vertical spaced
84.0 |
mm² 64.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Al 0.0 |
Conductor cross-section 25.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
95.0 |
B1 - Insulated conductors in conduit on a wooden wall
76.0 |
C - Single-core or multi-core cable on a wooden wall
117.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
93.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
119.0 |
F - Single-core flat cables, touching in free air
90.0 |
Ft - Single-core trefoil cables, touching in free air
96.0 |
G - Single-core horizontal spaced
75.0 |
Gv - Single-core flat vertical spaced
107.0 |
mm² 82.0 |
Cu 141.0 |
Al 103.0 |
Cu 135.0 |
Al 182.0 |
Cu 103.0 |
Al 138.0 |
Cu 161.0 |
Al 122.0 |
Conductor cross-section 35.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
117.0 |
B1 - Insulated conductors in conduit on a wooden wall
94.0 |
C - Single-core or multi-core cable on a wooden wall
144.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
116.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
147.0 |
F - Single-core flat cables, touching in free air
112.0 |
Ft - Single-core trefoil cables, touching in free air
115.0 |
G - Single-core horizontal spaced
90.0 |
Gv - Single-core flat vertical spaced
129.0 |
mm² 98.0 |
Cu 176.0 |
Al 129.0 |
Cu 169.0 |
Al 226.0 |
Cu 129.0 |
Al 172.0 |
Cu 201.0 |
Al 153.0 |
Conductor cross-section 50.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
141.0 |
B1 - Insulated conductors in conduit on a wooden wall
113.0 |
C - Single-core or multi-core cable on a wooden wall
175.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
140.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
179.0 |
F - Single-core flat cables, touching in free air
136.0 |
Ft - Single-core trefoil cables, touching in free air
135.0 |
G - Single-core horizontal spaced
106.0 |
Gv - Single-core flat vertical spaced
153.0 |
mm² 117.0 |
Cu 216.0 |
Al 159.0 |
Cu 207.0 |
Al 275.0 |
Cu 159.0 |
Al 210.0 |
Cu 246.0 |
Al 188.0 |
Conductor cross-section 70.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
179.0 |
B1 - Insulated conductors in conduit on a wooden wall
142.0 |
C - Single-core or multi-core cable on a wooden wall
222.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
179.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
229.0 |
F - Single-core flat cables, touching in free air
174.0 |
Ft - Single-core trefoil cables, touching in free air
167.0 |
G - Single-core horizontal spaced
130.0 |
Gv - Single-core flat vertical spaced
188.0 |
mm² 144.0 |
Cu 279.0 |
Al 206.0 |
Cu 268.0 |
Al 353.0 |
Cu 206.0 |
Al 271.0 |
Cu 318.0 |
Al 244.0 |
Conductor cross-section 95.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
216.0 |
B1 - Insulated conductors in conduit on a wooden wall
171.0 |
C - Single-core or multi-core cable on a wooden wall
269.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
217.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
278.0 |
F - Single-core flat cables, touching in free air
211.0 |
Ft - Single-core trefoil cables, touching in free air
197.0 |
G - Single-core horizontal spaced
154.0 |
Gv - Single-core flat vertical spaced
226.0 |
mm² 172.0 |
Cu 342.0 |
Al 253.0 |
Cu 328.0 |
Al 430.0 |
Cu 253.0 |
Al 332.0 |
Cu 389.0 |
Al 300.0 |
Conductor cross-section 120.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
249.0 |
B1 - Insulated conductors in conduit on a wooden wall
197.0 |
C - Single-core or multi-core cable on a wooden wall
312.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
251.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
322.0 |
F - Single-core flat cables, touching in free air
245.0 |
Ft - Single-core trefoil cables, touching in free air
223.0 |
G - Single-core horizontal spaced
174.0 |
Gv - Single-core flat vertical spaced
257.0 |
mm² 197.0 |
Cu 400.0 |
Al 296.0 |
Cu 383.0 |
Al 500.0 |
Cu 296.0 |
Al 387.0 |
Cu 454.0 |
Al 351.0 |
Conductor cross-section 150.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
285.0 |
B1 - Insulated conductors in conduit on a wooden wall
226.0 |
C - Single-core or multi-core cable on a wooden wall
342.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
267.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
371.0 |
F - Single-core flat cables, touching in free air
283.0 |
Ft - Single-core trefoil cables, touching in free air
251.0 |
G - Single-core horizontal spaced
197.0 |
Gv - Single-core flat vertical spaced
287.0 |
mm² 220.0 |
Cu 464.0 |
Al 343.0 |
Cu 444.0 |
Al 577.0 |
Cu 343.0 |
Al 448.0 |
Cu 527.0 |
Al 408.0 |
Conductor cross-section 185.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
324.0 |
B1 - Insulated conductors in conduit on a wooden wall
256.0 |
C - Single-core or multi-core cable on a wooden wall
384.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
300.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
424.0 |
F - Single-core flat cables, touching in free air
323.0 |
Ft - Single-core trefoil cables, touching in free air
281.0 |
G - Single-core horizontal spaced
220.0 |
Gv - Single-core flat vertical spaced
324.0 |
mm² 250.0 |
Cu 533.0 |
Al 395.0 |
Cu 510.0 |
Al 661.0 |
Cu 395.0 |
Al 515.0 |
Cu 605.0 |
Al 470.0 |
Conductor cross-section 240.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
380.0 |
B1 - Insulated conductors in conduit on a wooden wall
300.0 |
C - Single-core or multi-core cable on a wooden wall
450.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
351.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
500.0 |
F - Single-core flat cables, touching in free air
382.0 |
Ft - Single-core trefoil cables, touching in free air
324.0 |
G - Single-core horizontal spaced
253.0 |
Gv - Single-core flat vertical spaced
375.0 |
mm² 290.0 |
Cu 634.0 |
Al 471.0 |
Cu 607.0 |
Al 781.0 |
Cu 471.0 |
Al 611.0 |
Cu 719.0 |
Al 561.0 |
Conductor cross-section 300.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
435.0 |
B1 - Insulated conductors in conduit on a wooden wall
344.0 |
C - Single-core or multi-core cable on a wooden wall
514.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
402.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
576.0 |
F - Single-core flat cables, touching in free air
440.0 |
Ft - Single-core trefoil cables, touching in free air
365.0 |
G - Single-core horizontal spaced
286.0 |
Gv - Single-core flat vertical spaced
419.0 |
mm² 326.0 |
Cu 736.0 |
Al 547.0 |
Cu 703.0 |
Al 902.0 |
Cu 547.0 |
Al 708.0 |
Cu 833.0 |
Al 652.0 |
Current capacity table XLPE insulation single core single phase
Conductor cross-section | A1 - Insulated conductors in conduit in a thermally insulated wall | B1 - Insulated conductors in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | F - Single-core flat cables, touching in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
Conductor cross-section 1.5 |
A1 - Insulated conductors in conduit in a thermally insulated wall
19.0 |
B1 - Insulated conductors in conduit on a wooden wall
0.0 |
C - Single-core or multi-core cable on a wooden wall
23.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
0.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
24.0 |
F - Single-core flat cables, touching in free air
0.0 |
mm² 25.0 |
Cu 0.0 |
Al 27.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Conductor cross-section 2.5 |
A1 - Insulated conductors in conduit in a thermally insulated wall
26.0 |
B1 - Insulated conductors in conduit on a wooden wall
20.0 |
C - Single-core or multi-core cable on a wooden wall
31.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
25.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
33.0 |
F - Single-core flat cables, touching in free air
26.0 |
mm² 33.0 |
Cu 26.0 |
Al 35.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Conductor cross-section 4.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
35.0 |
B1 - Insulated conductors in conduit on a wooden wall
27.0 |
C - Single-core or multi-core cable on a wooden wall
42.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
33.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
45.0 |
F - Single-core flat cables, touching in free air
35.0 |
mm² 43.0 |
Cu 33.0 |
Al 46.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Conductor cross-section 6.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
45.0 |
B1 - Insulated conductors in conduit on a wooden wall
35.0 |
C - Single-core or multi-core cable on a wooden wall
54.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
43.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
58.0 |
F - Single-core flat cables, touching in free air
45.0 |
mm² 53.0 |
Cu 42.0 |
Al 58.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Conductor cross-section 10.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
61.0 |
B1 - Insulated conductors in conduit on a wooden wall
48.0 |
C - Single-core or multi-core cable on a wooden wall
75.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
59.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
80.0 |
F - Single-core flat cables, touching in free air
62.0 |
mm² 71.0 |
Cu 55.0 |
Al 77.0 |
Cu 0.0 |
Al 0.0 |
Cu 0.0 |
Conductor cross-section 16.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
81.0 |
B1 - Insulated conductors in conduit on a wooden wall
64.0 |
C - Single-core or multi-core cable on a wooden wall
100.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
79.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
107.0 |
F - Single-core flat cables, touching in free air
84.0 |
mm² 91.0 |
Cu 71.0 |
Al 100.0 |
Cu 76.0 |
Al 0.0 |
Cu 0.0 |
Conductor cross-section 25.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
106.0 |
B1 - Insulated conductors in conduit on a wooden wall
84.0 |
C - Single-core or multi-core cable on a wooden wall
133.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
105.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
138.0 |
F - Single-core flat cables, touching in free air
101.0 |
mm² 116.0 |
Cu 90.0 |
Al 129.0 |
Cu 98.0 |
Al 161.0 |
Cu 121.0 |
Conductor cross-section 35.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
131.0 |
B1 - Insulated conductors in conduit on a wooden wall
103.0 |
C - Single-core or multi-core cable on a wooden wall
164.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
130.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
171.0 |
F - Single-core flat cables, touching in free air
126.0 |
mm² 139.0 |
Cu 108.0 |
Al 155.0 |
Cu 117.0 |
Al 200.0 |
Cu 150.0 |
Conductor cross-section 50.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
158.0 |
B1 - Insulated conductors in conduit on a wooden wall
125.0 |
C - Single-core or multi-core cable on a wooden wall
198.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
157.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
209.0 |
F - Single-core flat cables, touching in free air
154.0 |
mm² 164.0 |
Cu 128.0 |
Al 183.0 |
Cu 139.0 |
Al 242.0 |
Cu 184.0 |
Conductor cross-section 70.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
200.0 |
B1 - Insulated conductors in conduit on a wooden wall
158.0 |
C - Single-core or multi-core cable on a wooden wall
253.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
200.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
269.0 |
F - Single-core flat cables, touching in free air
198.0 |
mm² 203.0 |
Cu 158.0 |
Al 225.0 |
Cu 170.0 |
Al 310.0 |
Cu 237.0 |
Conductor cross-section 95.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
241.0 |
B1 - Insulated conductors in conduit on a wooden wall
191.0 |
C - Single-core or multi-core cable on a wooden wall
306.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
242.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
328.0 |
F - Single-core flat cables, touching in free air
241.0 |
mm² 239.0 |
Cu 186.0 |
Al 270.0 |
Cu 204.0 |
Al 377.0 |
Cu 289.0 |
Conductor cross-section 120.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
278.0 |
B1 - Insulated conductors in conduit on a wooden wall
220.0 |
C - Single-core or multi-core cable on a wooden wall
354.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
281.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
382.0 |
F - Single-core flat cables, touching in free air
280.0 |
mm² 271.0 |
Cu 211.0 |
Al 306.0 |
Cu 233.0 |
Al 437.0 |
Cu 337.0 |
Conductor cross-section 150.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
318.0 |
B1 - Insulated conductors in conduit on a wooden wall
253.0 |
C - Single-core or multi-core cable on a wooden wall
393.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
307.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
441.0 |
F - Single-core flat cables, touching in free air
324.0 |
mm² 306.0 |
Cu 238.0 |
Al 343.0 |
Cu 261.0 |
Al 504.0 |
Cu 389.0 |
Conductor cross-section 185.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
362.0 |
B1 - Insulated conductors in conduit on a wooden wall
288.0 |
C - Single-core or multi-core cable on a wooden wall
449.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
351.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
506.0 |
F - Single-core flat cables, touching in free air
371.0 |
mm² 343.0 |
Cu 267.0 |
Al 387.0 |
Cu 296.0 |
Al 575.0 |
Cu 447.0 |
Conductor cross-section 240.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
424.0 |
B1 - Insulated conductors in conduit on a wooden wall
338.0 |
C - Single-core or multi-core cable on a wooden wall
528.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
412.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
599.0 |
F - Single-core flat cables, touching in free air
439.0 |
mm² 395.0 |
Cu 307.0 |
Al 448.0 |
Cu 343.0 |
Al 679.0 |
Cu 530.0 |
Conductor cross-section 300.0 |
A1 - Insulated conductors in conduit in a thermally insulated wall
486.0 |
B1 - Insulated conductors in conduit on a wooden wall
387.0 |
C - Single-core or multi-core cable on a wooden wall
603.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
471.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
693.0 |
F - Single-core flat cables, touching in free air
508.0 |
mm² 446.0 |
Cu 346.0 |
Al 502.0 |
Cu 386.0 |
Al 783.0 |
Cu 613.0 |
Current capacity table XLPE insulation multicore single phase
Conductor cross-section | A2 - Multi-core cable in conduit in a thermally insulated wall | B2 - Multi-core cable in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | E - Multi-core cable in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
Conductor cross-section 1.5 |
A2 - Multi-core cable in conduit in a thermally insulated wall
18.5 |
B2 - Multi-core cable in conduit on a wooden wall
0.0 |
C - Single-core or multi-core cable on a wooden wall
22.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
0.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
24.0 |
E - Multi-core cable in free air
0.0 |
mm² 25.0 |
Cu 0.0 |
Al 27.0 |
Cu 0.0 |
Al 26.0 |
Cu 0.0 |
Conductor cross-section 2.5 |
A2 - Multi-core cable in conduit in a thermally insulated wall
25.0 |
B2 - Multi-core cable in conduit on a wooden wall
19.5 |
C - Single-core or multi-core cable on a wooden wall
30.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
23.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
33.0 |
E - Multi-core cable in free air
26.0 |
mm² 33.0 |
Cu 26.0 |
Al 35.0 |
Cu 0.0 |
Al 36.0 |
Cu 28.0 |
Conductor cross-section 4.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
33.0 |
B2 - Multi-core cable in conduit on a wooden wall
26.0 |
C - Single-core or multi-core cable on a wooden wall
40.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
31.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
45.0 |
E - Multi-core cable in free air
35.0 |
mm² 43.0 |
Cu 33.0 |
Al 46.0 |
Cu 0.0 |
Al 49.0 |
Cu 38.0 |
Conductor cross-section 6.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
42.0 |
B2 - Multi-core cable in conduit on a wooden wall
33.0 |
C - Single-core or multi-core cable on a wooden wall
51.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
40.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
58.0 |
E - Multi-core cable in free air
45.0 |
mm² 53.0 |
Cu 42.0 |
Al 58.0 |
Cu 0.0 |
Al 63.0 |
Cu 49.0 |
Conductor cross-section 10.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
57.0 |
B2 - Multi-core cable in conduit on a wooden wall
45.0 |
C - Single-core or multi-core cable on a wooden wall
69.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
54.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
80.0 |
E - Multi-core cable in free air
62.0 |
mm² 71.0 |
Cu 55.0 |
Al 77.0 |
Cu 0.0 |
Al 86.0 |
Cu 67.0 |
Conductor cross-section 16.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
76.0 |
B2 - Multi-core cable in conduit on a wooden wall
60.0 |
C - Single-core or multi-core cable on a wooden wall
91.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
72.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
107.0 |
E - Multi-core cable in free air
84.0 |
mm² 91.0 |
Cu 71.0 |
Al 100.0 |
Cu 76.0 |
Al 115.0 |
Cu 91.0 |
Conductor cross-section 25.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
99.0 |
B2 - Multi-core cable in conduit on a wooden wall
78.0 |
C - Single-core or multi-core cable on a wooden wall
119.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
94.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
138.0 |
E - Multi-core cable in free air
101.0 |
mm² 116.0 |
Cu 90.0 |
Al 129.0 |
Cu 98.0 |
Al 149.0 |
Cu 108.0 |
Conductor cross-section 35.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
121.0 |
B2 - Multi-core cable in conduit on a wooden wall
96.0 |
C - Single-core or multi-core cable on a wooden wall
146.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
115.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
171.0 |
E - Multi-core cable in free air
126.0 |
mm² 139.0 |
Cu 108.0 |
Al 155.0 |
Cu 117.0 |
Al 185.0 |
Cu 135.0 |
Conductor cross-section 50.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
145.0 |
B2 - Multi-core cable in conduit on a wooden wall
115.0 |
C - Single-core or multi-core cable on a wooden wall
175.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
138.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
209.0 |
E - Multi-core cable in free air
154.0 |
mm² 164.0 |
Cu 128.0 |
Al 183.0 |
Cu 139.0 |
Al 225.0 |
Cu 164.0 |
Conductor cross-section 70.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
183.0 |
B2 - Multi-core cable in conduit on a wooden wall
145.0 |
C - Single-core or multi-core cable on a wooden wall
221.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
175.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
269.0 |
E - Multi-core cable in free air
198.0 |
mm² 203.0 |
Cu 158.0 |
Al 225.0 |
Cu 170.0 |
Al 289.0 |
Cu 211.0 |
Conductor cross-section 95.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
220.0 |
B2 - Multi-core cable in conduit on a wooden wall
175.0 |
C - Single-core or multi-core cable on a wooden wall
265.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
210.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
328.0 |
E - Multi-core cable in free air
241.0 |
mm² 239.0 |
Cu 186.0 |
Al 270.0 |
Cu 204.0 |
Al 352.0 |
Cu 257.0 |
Conductor cross-section 120.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
253.0 |
B2 - Multi-core cable in conduit on a wooden wall
201.0 |
C - Single-core or multi-core cable on a wooden wall
305.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
242.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
382.0 |
E - Multi-core cable in free air
280.0 |
mm² 271.0 |
Cu 211.0 |
Al 306.0 |
Cu 233.0 |
Al 410.0 |
Cu 300.0 |
Conductor cross-section 150.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
290.0 |
B2 - Multi-core cable in conduit on a wooden wall
230.0 |
C - Single-core or multi-core cable on a wooden wall
334.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
261.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
441.0 |
E - Multi-core cable in free air
324.0 |
mm² 306.0 |
Cu 238.0 |
Al 343.0 |
Cu 261.0 |
Al 473.0 |
Cu 346.0 |
Conductor cross-section 185.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
329.0 |
B2 - Multi-core cable in conduit on a wooden wall
262.0 |
C - Single-core or multi-core cable on a wooden wall
384.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
300.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
506.0 |
E - Multi-core cable in free air
371.0 |
mm² 343.0 |
Cu 267.0 |
Al 387.0 |
Cu 296.0 |
Al 542.0 |
Cu 397.0 |
Conductor cross-section 240.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
386.0 |
B2 - Multi-core cable in conduit on a wooden wall
307.0 |
C - Single-core or multi-core cable on a wooden wall
459.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
358.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
599.0 |
E - Multi-core cable in free air
439.0 |
mm² 395.0 |
Cu 307.0 |
Al 448.0 |
Cu 343.0 |
Al 641.0 |
Cu 470.0 |
Conductor cross-section 300.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
442.0 |
B2 - Multi-core cable in conduit on a wooden wall
352.0 |
C - Single-core or multi-core cable on a wooden wall
532.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
415.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
693.0 |
E - Multi-core cable in free air
508.0 |
mm² 446.0 |
Cu 346.0 |
Al 502.0 |
Cu 386.0 |
Al 741.0 |
Cu 543.0 |
Current capacity table XLPE insulation multicore three phase
Conductor cross-section | A2 - Multi-core cable in conduit in a thermally insulated wall | B2 - Multi-core cable in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | E - Multi-core cable in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
Conductor cross-section 1.5 |
A2 - Multi-core cable in conduit in a thermally insulated wall
16.5 |
B2 - Multi-core cable in conduit on a wooden wall
0.0 |
C - Single-core or multi-core cable on a wooden wall
19.5 |
D1 - Single-core or Multi-core cable in ducts in the ground
0.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
22.0 |
E - Multi-core cable in free air
0.0 |
mm² 25.0 |
Cu 0.0 |
Al 23.0 |
Cu 0.0 |
Al 26.0 |
Cu 0.0 |
Conductor cross-section 2.5 |
A2 - Multi-core cable in conduit in a thermally insulated wall
22.0 |
B2 - Multi-core cable in conduit on a wooden wall
19.5 |
C - Single-core or multi-core cable on a wooden wall
26.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
23.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
30.0 |
E - Multi-core cable in free air
26.0 |
mm² 33.0 |
Cu 26.0 |
Al 30.0 |
Cu 0.0 |
Al 36.0 |
Cu 28.0 |
Conductor cross-section 4.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
30.0 |
B2 - Multi-core cable in conduit on a wooden wall
26.0 |
C - Single-core or multi-core cable on a wooden wall
35.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
31.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
40.0 |
E - Multi-core cable in free air
35.0 |
mm² 43.0 |
Cu 33.0 |
Al 39.0 |
Cu 0.0 |
Al 49.0 |
Cu 38.0 |
Conductor cross-section 6.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
38.0 |
B2 - Multi-core cable in conduit on a wooden wall
33.0 |
C - Single-core or multi-core cable on a wooden wall
44.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
40.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
52.0 |
E - Multi-core cable in free air
45.0 |
mm² 53.0 |
Cu 42.0 |
Al 49.0 |
Cu 0.0 |
Al 63.0 |
Cu 49.0 |
Conductor cross-section 10.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
51.0 |
B2 - Multi-core cable in conduit on a wooden wall
45.0 |
C - Single-core or multi-core cable on a wooden wall
60.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
54.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
71.0 |
E - Multi-core cable in free air
62.0 |
mm² 71.0 |
Cu 55.0 |
Al 65.0 |
Cu 0.0 |
Al 86.0 |
Cu 67.0 |
Conductor cross-section 16.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
68.0 |
B2 - Multi-core cable in conduit on a wooden wall
60.0 |
C - Single-core or multi-core cable on a wooden wall
80.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
72.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
96.0 |
E - Multi-core cable in free air
84.0 |
mm² 91.0 |
Cu 71.0 |
Al 84.0 |
Cu 76.0 |
Al 115.0 |
Cu 91.0 |
Conductor cross-section 25.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
89.0 |
B2 - Multi-core cable in conduit on a wooden wall
78.0 |
C - Single-core or multi-core cable on a wooden wall
105.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
94.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
119.0 |
E - Multi-core cable in free air
101.0 |
mm² 116.0 |
Cu 90.0 |
Al 107.0 |
Cu 98.0 |
Al 149.0 |
Cu 108.0 |
Conductor cross-section 35.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
109.0 |
B2 - Multi-core cable in conduit on a wooden wall
96.0 |
C - Single-core or multi-core cable on a wooden wall
128.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
115.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
147.0 |
E - Multi-core cable in free air
126.0 |
mm² 139.0 |
Cu 108.0 |
Al 129.0 |
Cu 117.0 |
Al 185.0 |
Cu 135.0 |
Conductor cross-section 50.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
130.0 |
B2 - Multi-core cable in conduit on a wooden wall
115.0 |
C - Single-core or multi-core cable on a wooden wall
154.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
138.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
179.0 |
E - Multi-core cable in free air
154.0 |
mm² 164.0 |
Cu 128.0 |
Al 153.0 |
Cu 139.0 |
Al 225.0 |
Cu 164.0 |
Conductor cross-section 70.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
164.0 |
B2 - Multi-core cable in conduit on a wooden wall
145.0 |
C - Single-core or multi-core cable on a wooden wall
194.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
175.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
229.0 |
E - Multi-core cable in free air
198.0 |
mm² 203.0 |
Cu 158.0 |
Al 188.0 |
Cu 170.0 |
Al 289.0 |
Cu 211.0 |
Conductor cross-section 95.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
197.0 |
B2 - Multi-core cable in conduit on a wooden wall
175.0 |
C - Single-core or multi-core cable on a wooden wall
233.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
210.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
278.0 |
E - Multi-core cable in free air
241.0 |
mm² 239.0 |
Cu 186.0 |
Al 226.0 |
Cu 204.0 |
Al 352.0 |
Cu 257.0 |
Conductor cross-section 120.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
227.0 |
B2 - Multi-core cable in conduit on a wooden wall
201.0 |
C - Single-core or multi-core cable on a wooden wall
268.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
242.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
322.0 |
E - Multi-core cable in free air
280.0 |
mm² 271.0 |
Cu 211.0 |
Al 257.0 |
Cu 233.0 |
Al 410.0 |
Cu 300.0 |
Conductor cross-section 150.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
259.0 |
B2 - Multi-core cable in conduit on a wooden wall
230.0 |
C - Single-core or multi-core cable on a wooden wall
300.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
261.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
371.0 |
E - Multi-core cable in free air
324.0 |
mm² 306.0 |
Cu 238.0 |
Al 287.0 |
Cu 261.0 |
Al 473.0 |
Cu 346.0 |
Conductor cross-section 185.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
295.0 |
B2 - Multi-core cable in conduit on a wooden wall
262.0 |
C - Single-core or multi-core cable on a wooden wall
340.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
300.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
424.0 |
E - Multi-core cable in free air
371.0 |
mm² 343.0 |
Cu 267.0 |
Al 324.0 |
Cu 296.0 |
Al 542.0 |
Cu 397.0 |
Conductor cross-section 240.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
346.0 |
B2 - Multi-core cable in conduit on a wooden wall
307.0 |
C - Single-core or multi-core cable on a wooden wall
398.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
358.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
500.0 |
E - Multi-core cable in free air
439.0 |
mm² 395.0 |
Cu 307.0 |
Al 375.0 |
Cu 343.0 |
Al 641.0 |
Cu 470.0 |
Conductor cross-section 300.0 |
A2 - Multi-core cable in conduit in a thermally insulated wall
396.0 |
B2 - Multi-core cable in conduit on a wooden wall
352.0 |
C - Single-core or multi-core cable on a wooden wall
455.0 |
D1 - Single-core or Multi-core cable in ducts in the ground
415.0 |
D2 - Single-core or Multi-core cables designed to be buried directly in the ground
576.0 |
E - Multi-core cable in free air
508.0 |
mm² 446.0 |
Cu 346.0 |
Al 419.0 |
Cu 386.0 |
Al 741.0 |
Cu 543.0 |
Our websites