RETFLEX-FOC® RV-K 1x50 CPR Eca

Description

Description

Standards

  • Product
    IEC 60502
  • Test
    IEEE 383

Installation

These cables can be fixed on cable trays, within conduits or fixed to walls. They also can be buried directly with extra mechanical protection.

Core colours

  • 2 cores = Brown + Light blue
  • 3 cores = Brown + Black + Grey or Light blue + Brown + Green-Yellow
  • 4 cores = Black + Grey + Brown + Light blue or Green-Yellow
  • 5 cores = Black + Light blue + Brown + Grey + Green-Yellow
  • > 5 cores = 1 Green-Yellow + others Black conductors numbered

Marking

Nexans 305  RV-K 0.6/1 kV  UNE 21123  n(G or x) s RETFOC Eca AENOR YYYY

  • n = number of cores
  • G = with Green-Yellow
  • x = without Green-Yellow
  • s = section in mm²
  • YYYY = year

Gama compatible con MOBIWAY MOB

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Flexible class 5
Conductor material
Bare copper
Insulation
XLPE (chemical)
Outer sheath
PVC
Sheath colour
Black
With Green/Yellow core
No
Lead free
Yes
Conductor shape
Circular
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Average insulation thickness
- mm
Number of cores
1
Conductor cross-section
50 mm²
Approximate weight
518 kg/km
Maximum outer diameter
14.2 mm
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
- Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Permissible current rating when buried
- A
Permissible current rating in open air
- A

Mechanical characteristics

Mechanical characteristics

Cable flexibility
Flexible
Mechanical resistance to impacts
Low

Usage characteristics

Usage characteristics

Chemical resistance
Accidental
Length
- m
Max. conductor temperature in service
90 °C
Operating temperature, range
-5 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Weather resistance
Very good
Flame retardant
EN 50265-2-1
Packaging
Drum
Water proof
Good

Resources

Resources

Documentation

Current capacity table XLPE insulation single core three phase

Conductor cross-section A1 - Insulated conductors in conduit in a thermally insulated wall B1 - Insulated conductors in conduit on a wooden wall C - Single-core or multi-core cable on a wooden wall D1 - Single-core or Multi-core cable in ducts in the ground D2 - Single-core or Multi-core cables designed to be buried directly in the ground F - Single-core flat cables, touching in free air Ft - Single-core trefoil cables, touching in free air G - Single-core horizontal spaced Gv - Single-core flat vertical spaced
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
50.0 141.0 113.0 175.0 140.0 179.0 136.0 135.0 106.0 153.0 117.0 216.0 159.0 207.0 275.0 159.0 210.0 246.0 188.0

Current capacity table XLPE insulation single core single phase

Conductor cross-section A1 - Insulated conductors in conduit in a thermally insulated wall B1 - Insulated conductors in conduit on a wooden wall C - Single-core or multi-core cable on a wooden wall D1 - Single-core or Multi-core cable in ducts in the ground D2 - Single-core or Multi-core cables designed to be buried directly in the ground F - Single-core flat cables, touching in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
50.0 158.0 125.0 198.0 157.0 209.0 154.0 164.0 128.0 183.0 139.0 242.0 184.0

Current capacity table XLPE insulation multicore single phase

Conductor cross-section A2 - Multi-core cable in conduit in a thermally insulated wall B2 - Multi-core cable in conduit on a wooden wall C - Single-core or multi-core cable on a wooden wall D1 - Single-core or Multi-core cable in ducts in the ground D2 - Single-core or Multi-core cables designed to be buried directly in the ground E - Multi-core cable in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
50.0 145.0 115.0 175.0 138.0 209.0 154.0 164.0 128.0 183.0 139.0 225.0 164.0

Current capacity table XLPE insulation multicore three phase

Conductor cross-section A2 - Multi-core cable in conduit in a thermally insulated wall B2 - Multi-core cable in conduit on a wooden wall C - Single-core or multi-core cable on a wooden wall D1 - Single-core or Multi-core cable in ducts in the ground D2 - Single-core or Multi-core cables designed to be buried directly in the ground E - Multi-core cable in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
50.0 130.0 115.0 154.0 138.0 179.0 154.0 164.0 128.0 153.0 139.0 225.0 164.0

Declaration of Performance

  • Declaration of Performance n� : 1000232-ESPO
  • Certification Date : 9/15/21
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : NB 1722
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close