ALSECURE-K 1X16 Brown GL6000
ALSECURE-K 1X16 Brown GL6000
Nexans H07Z1-K are used for fixed secured installations
Read more- Nexans ref. : 10093188
- Country ref. : 102 - 336
- EAN : 3427500012703
Description
Description
Standards
-
ProductEN 50525-3-31; EN 50575; IEC 60228; UNE 21022; UNE 211002
-
TestEN 50266-2-4; EN 50267-2-2; IEC 60332-1; IEC 60332-3-24; IEC 61034-2; NF C32-070/C2; UNE EN 50267-2-3 ; UNE-EN 50265-2-1
Application
Flexible insulated conductors Nexans H07Z1-K are used for fixed secured protected installation.
Halogen free, fire retardant with low emission of smoke, Nexans H07Z1-K may be used in public buildings or areas where fire safety is concerned
Installation
Nexans H07Z1-K can be installed in open air, in conduit, in cable ducting, in switch cabinets.
Thanks to the sliding properties of the insulation, installation is made easier while pulling in...
Encuentra este producto en EASYCALC™
New cardboard packaging for H07V-K and H07Z1-K
Color code for Nexans Alsecure H07Z1-K cross-section
Cable colors available
-
-
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Documentation
Current capacity table PVC insulation multicore three phase
Conductor cross-section | A2 - Multi-core cable in conduit in a thermally insulated wall | B2 - Multi-core cable in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | E - Multi-core cable in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
16.0 | 52.0 | 41.0 | 62.0 | 48.0 | 76.0 | 59.0 | 64.0 | 50.0 | 70.0 | 53.0 | 80.0 | 61.0 |
Current capacity table PVC insulation multicore single phase
Conductor cross-section | A2 - Multi-core cable in conduit in a thermally insulated wall | B2 - Multi-core cable in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | E - Multi-core cable in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
16.0 | 57.0 | 44.0 | 69.0 | 54.0 | 85.0 | 66.0 | 78.0 | 61.0 | 83.0 | 63.0 | 94.0 | 73.0 |
Current capacity table PVC insulation single core three phase
Conductor cross-section | A1 - Insulated conductors in conduit in a thermally insulated wall | B1 - Insulated conductors in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | F - Single-core flat cables, touching in free air | Ft - Single-core trefoil cables, touching in free air | G - Single-core horizontal spaced | Gv - Single-core flat vertical spaced | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
16.0 | 56.0 | 43.0 | 68.0 | 53.0 | 76.0 | 59.0 | 64.0 | 50.0 | 70.0 | 53.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
Current capacity table PVC insulation single core single phase
Conductor cross-section | A1 - Insulated conductors in conduit in a thermally insulated wall | B1 - Insulated conductors in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | F - Single-core flat cables, touching in free air | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
16.0 | 61.0 | 48.0 | 76.0 | 60.0 | 85.0 | 66.0 | 78.0 | 61.0 | 83.0 | 63.0 | 0.0 | 0.0 |
Selling & delivery Information
Ink jet marking
USE - HAR- ALSECURE H07Z1-K (AS) TYPE 2 AENOR PLANT N° NEXANS – DAY YEAR
Declaration of Performance
- Declaration of Performance n� : 1000150-FRAU
- Certification Date : 1/28/21
- AVCP (Assessment and Verification of Constancy of Performance) : System 1+
- Notified body : NB 099
- Declared performance : Cca-s1b,d1,a1