RV 0.6/1 KV 5G2.5 CREAM R100 P2.4Km

Description

Description

Standards

  • Product
    IEC 60502-1

Application

These RV 0.6/1Kv cables with XLPE insulation and PVC outer sheath can be used in all low voltage power installations. Multiconductors cables are adapted to remote control and telecontrol installations.

 

METRIUM™ metric marking is available for all packaging in coil)

 

Installation

These cables can be fixed on cable trays, within conduits or fixed to walls, installed outside. They also can be buried directly with extra mechanical protection.

 

Marking

NEXANS Factory n°  RV 0.6/1kV n (G) s mm² IEC 60502 90° Eca

  • n = number of cores
  • s = section in mm²
  • G = with Green-Yellow

 

Permissible current and voltage drop are given


a) in free air, sheltered from sun, on cable tray or bracket, on cable ladder, and spaced from the wall, temperature = 30°C.
b) buried with thermal resistivity of the ground 1Km/W, laying depth : 600 mm, temperature = 20°C.

If conditions are differents, apply correction factors from NF C 15-100 standard  or equivalent national standard

 

Voltage drop

Calculated with cos φ = 0,8

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor flexibility
Solid class 1
Conductor material
Bare copper
Insulation
XLPE
Outer sheath
PVC
Sheath colour
Cream
With Green/Yellow core
Yes
With smaller neutral conductor
No
Conductor shape
Circular
Lead free
Yes

Dimensional characteristics

Dimensional characteristics

Number of cores
5
Conductor cross-section
2.5 mm²
Approximate weight
200 kg/km
Maximum outer diameter
14.5 mm
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Permissible current rating in open air
31 A
Permissible current rating when buried
41 A
Voltage drop, 3 conductors
- V/A.km
Voltage drop, single phase
- V/A.km

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
-
Cable flexibility
Rigid

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Operating temperature, range
-15 ... 90 °C
Flame retardant
C2, NF C 32-070
Weather resistance
Good
Chemical resistance
Accidental
Water proof
Intermittent
Packaging
Coil
Length
100 m
Laying operation bending radius
174 mm
Minimum static operating bending radius
78 mm

Resources

Resources

Documentation

PEP RV CREME pdf — 4.4 MB

Declaration of Performance

  • Declaration of Performance n� : 1000762-FRAU-004
  • Certification Date : 11/14/18
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : NB 1812
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close